Power System Telemechanics Electricity UPS System With PDU Series
Feeder
Electricity UPS System consist of:
Electrical UPS, DBW bypass stablalized cabinet, and feeder cabinet
of PDU series.
Product Introduction:
It possesses on-line double conversion and zero switch function.
After being isolated and filtered by regulator, Single-phase 220V
or three-phase 380V can provide stable power for load through
inverter when the AC is normal. If the failure of AC power grid
supply or a power cut occurs, direct current panel, the backup of
power system, can invert to supply electricity through non-return
diode. If the direct current panel is under voltage or cut off,
static switch can shift to bypass stabilized cabinet to supply
electricity. When the AC power becomes normal, the static switch
automatically shift to AC power grid to supply electricity
reversely. If the inverter is overloaded or the fault occurs to it,
the static switch shift to bypass stabilized cabinet to supply
electricity and indicates a warning signal at the same time.
Key Features:
Mainly Application:
Power system telemechanics, PTU, power line communication, power
system monitoring and etc
Specification:
CND310 10KVA-100KVA | ||||||||||||||
Model (KVA) | 10 | 15 | 20 | 30 | 40 | 50 | 60 | 80 | 100 | |||||
Rating capacity(KW) | 8 | 12 | 16 | 24 | 32 | 40 | 48 | 64 | 80 | |||||
Rating voltage | 220V(one-phase) /380V(three phase) | |||||||||||||
AC input | ||||||||||||||
Voltage range | ±25% | |||||||||||||
Frequency range | 50,60Hz±10% | |||||||||||||
Soft start | 0-100% in 5” | |||||||||||||
Power factor | 0.95(with input filter) | |||||||||||||
Bypass input | ||||||||||||||
Permitted voltage range | ±15% | |||||||||||||
Frequency range | 50/60Hz±5% | |||||||||||||
Output | ||||||||||||||
Voltage accuracy | 220V±1%(steady load) 220V±3%( fluctuating load) | |||||||||||||
Permitted Frequency range | 50/60Hz±0.05Hz(powered by battery) | |||||||||||||
Power factor | 0.8 | |||||||||||||
THD | Linearload<2%, non linear load<4% | |||||||||||||
Dynamic transients | <5% | |||||||||||||
Current crest ratio | 3:1 | |||||||||||||
Overload capacity | Normal in 110% load, 125% for 10min | |||||||||||||
Efficiency | Double switch:94%, ECO:98% | |||||||||||||
DC | ||||||||||||||
Battery voltage | 220V | |||||||||||||
Cutoff voltage | 185V | |||||||||||||
Maximum discharge current | 36A | 55A | 73A | 109A | 145A | 181A | 218A | 291A | 364A | |||||
Penal display | ||||||||||||||
LCD | Chinese/English UPS status, operation instruction input voltage, output voltage, current, frequency, battery voltage, value of charge and discharge current, accident display, warning | |||||||||||||
Unique option |
| |||||||||||||
Environment | ||||||||||||||
Temperature | 0ºC-40 ºC | |||||||||||||
Humidity | 0-95%(no condensing) | |||||||||||||
Storage temperature | -25 ºC—55 ºC | |||||||||||||
Altitude | <1500m |
Shenzhen Consnant Technology Co., Ltd.
Shenzhen CONSNANT Technology Co., Ltd. (simple name: CONSNANT) is a professional manufacturer engaged in research, development and production of UPS (Uninterruptible Power Supply) including the Modular UPS, Outdoor & Indoor UPS,Industrial special UPS, Low Frequency & High Frequency Online UPS and Solar Power System both for home appliance and telecom equipments.